OEM Isolation Switch Factory – SURGE ARRESTER FORM 60KV TO 245KV – Jonchn

Read More>>


Product Detail

Product Tags

Related Video

Feedback (2)

To create more benefit for buyers is our business philosophy; shopper growing is our working chase for Pgl Circuit Breaker, Single Phase Stabilizers, Polyphaser Lightning Arrestor, We are now on the lookout ahead to even larger cooperation with abroad consumers dependant on mutual added benefits. When you are interested in almost any of our products, be sure to experience cost-free to make contact with us for more facts.
OEM Isolation Switch Factory – SURGE ARRESTER FORM 60KV TO 245KV – Jonchn Detail:

Feature

Zinc oxide without spark gap with synthetic cover.
•Varistors have the ability to instantly switch from an insulating state to a conductive state in the event of an overvoltage,
•The composite structure in fiberglass impregnated with epoxy resin ensures the mechanical strength of the stack,
•The outer silicone elastomer shell provides dielectric strength.
Reference standards:IEC 60099-4 – 10 kA,20kA / class 2~4, IEC 60815 – pollution level IV

Performance

Nominal discharge current:10 kA (8/20 wave)
Large amplitude current:100 kA (wave 4/10)
Rated voltage:from 60kV to 216 kV
Creepage line:> 31 mm / kV
(level IV according to IEC 60815)
Energy capacity(mim):4.8 kJ / kV from Uc (wave 4/10)
Long time current(min):600 A (wave 2 ms)
Resistance to short-circuit currents: 31.5 kA / 0.2 s – 600 A / 1 s
•High flow power,
•Lowering of the residual voltage level,
•Minimal Joule losses,
•Stability of characteristics over time
•Simple installation,
•Maintenance free.

Installation conditions

•For indoors and outdoors;
•Ambient air temperature :-40℃~+45℃
•Maximum solar radiation not exceeding 1.1kW/m2;
•Altitude not exceeding 3000m;
•Rated frequency for a.c. system : 48Hz~62Hz;
•Maximum wind velocity not over 40m/s;
•Earthquake intensity not exceeding 8 degree;
•Power-frequency voltage applied continuously between the terminals of the arrester not over exceeding its continuous operating voltage;

Parameters data

Rated voltage

kV

60

72

84

96

108

120

132

144

168

192

204

216

Continuous operating voltage

kV

48

58

67.2

75

84

98

106

115

131

152

160

168

Maximum residual voltage at 5 kA 8/20µs

kV peak

148.6

178.3

208.0

237.8

262.4

291.6

320.8

349.9

408.2

466.6

495.7

524.9

Maximum residual voltage at 10 kA 8/20µs

kV peak

154.8

185.8

216.7

247.7

272.2

302.4

332.6

362.9

423.4

483.8

514.1

544.3

Maximum residual voltage at 20 kA 8/20µs

kV peak

166.6

199.9

233.2

266.6

291.6

324.0

356.4

388.8

453.6

518.4

550.8

583.2

Switching residual voltage at 500A – 30/80µs

kV peak

117.9

141.5

165.1

188.6

212.2

235.8

259.4

283.0

330.1

377.3

400.9

424.4

Steep current impulse residual voltage at 10kA – 1/2,5µs

kV peak

166.5

199.8

233.1

266.4

299.7

333.0

366.3

399.6

466.2

532.8

566.1

599.4

未标题-1
2

Device dimensions

 

10kA

60kV

72kV

84kV

96kV

108kV

120kV

132kV

144kV

168kV

192kV

204kV

216kV

A

90

112

B

210

232

C

174

196

H

Customized according to customer requirements

Creepage

distance

(mm)

 

Customized according to customer requirements

(All dimensions in mm.)

 

 

 


Product detail pictures:

OEM Isolation Switch Factory –  SURGE ARRESTER FORM 60KV TO 245KV – Jonchn detail pictures

OEM Isolation Switch Factory –  SURGE ARRESTER FORM 60KV TO 245KV – Jonchn detail pictures

OEM Isolation Switch Factory –  SURGE ARRESTER FORM 60KV TO 245KV – Jonchn detail pictures


Related Product Guide:

We can constantly satisfy our respected customers with our good high quality, good price tag and good support due to we have been additional specialist and extra hard-working and do it in cost-effective way for OEM Isolation Switch Factory – SURGE ARRESTER FORM 60KV TO 245KV – Jonchn , The product will supply to all over the world, such as: Jamaica, Singapore, Afghanistan, Ensuring high product quality by choosing the best suppliers, we have also implemented comprehensive quality control processes throughout our sourcing procedures. Meanwhile, our access to a large range of factories, coupled with our excellent management, also ensures that we can quickly fill your requirements at the best prices, regardless the order size.
  • The supplier abide the theory of "quality the basic, trust the first and management the advanced" so that they can ensure a reliable product quality and stable customers.
    5 Stars By Eleanore from Israel - 2017.03.07 13:42
    It is not easy to find such a professional and responsible provider in today's time. Hope that we can maintain long-term cooperation.
    5 Stars By Polly from Liberia - 2018.12.10 19:03