China Wholesale Power And Distribution Transformer Manufacturer – SURGE ARRESTER FORM 60KV TO 245KV – Jonchn Detail:
Feature
Zinc oxide without spark gap with synthetic cover.
•Varistors have the ability to instantly switch from an insulating state to a conductive state in the event of an overvoltage,
•The composite structure in fiberglass impregnated with epoxy resin ensures the mechanical strength of the stack,
•The outer silicone elastomer shell provides dielectric strength.
Reference standards:IEC 60099-4 – 10 kA,20kA / class 2~4, IEC 60815 – pollution level IV
Performance
Nominal discharge current:10 kA (8/20 wave)
Large amplitude current:100 kA (wave 4/10)
Rated voltage:from 60kV to 216 kV
Creepage line:> 31 mm / kV
(level IV according to IEC 60815)
Energy capacity(mim):4.8 kJ / kV from Uc (wave 4/10)
Long time current(min):600 A (wave 2 ms)
Resistance to short-circuit currents: 31.5 kA / 0.2 s – 600 A / 1 s
•High flow power,
•Lowering of the residual voltage level,
•Minimal Joule losses,
•Stability of characteristics over time
•Simple installation,
•Maintenance free.
Installation conditions
•For indoors and outdoors;
•Ambient air temperature :-40℃~+45℃
•Maximum solar radiation not exceeding 1.1kW/m2;
•Altitude not exceeding 3000m;
•Rated frequency for a.c. system : 48Hz~62Hz;
•Maximum wind velocity not over 40m/s;
•Earthquake intensity not exceeding 8 degree;
•Power-frequency voltage applied continuously between the terminals of the arrester not over exceeding its continuous operating voltage;
Parameters data
Rated voltage |
kV |
60 |
72 |
84 |
96 |
108 |
120 |
132 |
144 |
168 |
192 |
204 |
216 |
Continuous operating voltage |
kV |
48 |
58 |
67.2 |
75 |
84 |
98 |
106 |
115 |
131 |
152 |
160 |
168 |
Maximum residual voltage at 5 kA 8/20µs |
kV peak |
148.6 |
178.3 |
208.0 |
237.8 |
262.4 |
291.6 |
320.8 |
349.9 |
408.2 |
466.6 |
495.7 |
524.9 |
Maximum residual voltage at 10 kA 8/20µs |
kV peak |
154.8 |
185.8 |
216.7 |
247.7 |
272.2 |
302.4 |
332.6 |
362.9 |
423.4 |
483.8 |
514.1 |
544.3 |
Maximum residual voltage at 20 kA 8/20µs |
kV peak |
166.6 |
199.9 |
233.2 |
266.6 |
291.6 |
324.0 |
356.4 |
388.8 |
453.6 |
518.4 |
550.8 |
583.2 |
Switching residual voltage at 500A – 30/80µs |
kV peak |
117.9 |
141.5 |
165.1 |
188.6 |
212.2 |
235.8 |
259.4 |
283.0 |
330.1 |
377.3 |
400.9 |
424.4 |
Steep current impulse residual voltage at 10kA – 1/2,5µs |
kV peak |
166.5 |
199.8 |
233.1 |
266.4 |
299.7 |
333.0 |
366.3 |
399.6 |
466.2 |
532.8 |
566.1 |
599.4 |
Device dimensions
10kA |
60kV |
72kV |
84kV |
96kV |
108kV |
120kV |
132kV |
144kV |
168kV |
192kV |
204kV |
216kV |
A |
90 |
112 |
||||||||||
B |
210 |
232 |
||||||||||
C |
174 |
196 |
||||||||||
H |
Customized according to customer requirements |
|||||||||||
Creepage distance (mm) |
Customized according to customer requirements |
(All dimensions in mm.)
Product detail pictures:
Related Product Guide:
Our products are widely recognized and trusted by users and can meet continuously developing economic and social needs for China Wholesale Power And Distribution Transformer Manufacturer – SURGE ARRESTER FORM 60KV TO 245KV – Jonchn , The product will supply to all over the world, such as: Nairobi, Georgia, Egypt, Our domestic website's generated over 50, 000 purchasing orders every year and quite successful for internet shopping in Japan. We would be happy to have an opportunity to do business with your company. Looking forward to receiving your message !