● Meet the national standard GB17945- 2010 “fire emergency lighting and evacuation indicating system”.
● Cabinet type emergency lighting controller has four extension circuits, each extension circuit can carry 32 c e n t r a l i z e d p o w e r s u p p l y a n d distribution of electric device at most; Wall-mounted master machine has one extension circuit and can carry 40 units (16 sets of centralized power supply, 24 sets of distribution electric device)

Read More>>


Product Detail

Product Tags

Overview

● Meet the national standard GB17945-2010 "fire emergency lighting and evacuation indicating system”.
● Cabinet type emergency lighting controller has four extension circuits, each extension circuit can carry 32 centralized power supply and distribution of electric device at most; Wall-mounted master machine has one extension circuit and can carry 40 units (16 sets of centralized power supply, 24 sets of distribution electric device).
● A distribution electric device has four or eight lighting loops, each loop can be adapted with 64 sets of centralized control fire emergency lighting, therefore, the maximum capacity of one distribution electric device is 64 * 4 = 256 (or 512), and one cabinet type controller should be controlled within 6000 at best while a wall-mounted controller best controlled within 1000.
● Emergency lighting controller can communicate with fire alarm controller through RS232, CAN, or the network interface, receive the detector alarm information and heip evacuate. It can also receive the monitoring state of fire compartment through the 4 way switch vaule and enforce the evacuation according to the predetermined evacuation plan.
● Emergency lighting controller adopts the embedded industrial control system with 17-inch LCD host cabinet (7 inches for wall type). Device information, alarm text information and architectural graphics can be directly shown on the LCD screen, which is rich in content and user-friendly.
● Emergency lighting controller adopts double CPU host backup design. When the main CPU works in an abnormal way, it can automatically switch to standby CPU to ensure that emergency lighting controller host is always in the best working state and no delay into emergency evacuation control in the event of a fire.
● Emergency lighting controller has the function of SMS notification, when the controller monitors that event occurs, it will immediately inform the personnel on duty or the owner by text messages.
● System will automatically generate an evacuation path according to the fire alarm information, combined with the feature of building structure, evacuation path width, personnel load information, which is simple and flexible in programming.
● User operation classification and grading operation passwords can be set.
● Can check historical record, storage record number≥10000 pcs.
● Working temperature:-10℃-+55℃, humidity:〈95%RH

Centralized control type I

201711280354530102

Centralized control type II

201711280355097602

Centralized control type III

201711280355211977

Technical Index

● Cabinet host adopts standard 19-inch cabinet structure; Wall-mounted host adopts front single door closed structure, see right picture.
● Mainboard adopts embedded industrial mainboard with two CPU backup design, which is stable and reliable in operation;
● Cabinet host uses 17-inch LCD display screen with graphic display function, which is intuitive and rich in content;
● Monthly inspection on the 10th of each month from February to December, annual inspection on January 10th , after monthly inspection and annual inspection, it will recover automatically;
● Manual and automatic control function, it can generate evacuation path to ensure personnel safety and leave quickly according to the trend of fire spread information under automatic control function;
● It can print all event information with thermal printers;
● With a variety of information and communication interface, with strong information interaction ability, with functions of SMS notification;
● With black box function, can store more than 10000 pcs of historical records;
● The main electric power supply adopts special fire power while standby power adopts high-performance maintenance-free lead-acid batteries;
● power supply: AC220V/50Hz, 370W(cabinet host); 110W(wall-mounted host)
● cabinet host size: 600×600×1855(mm); wall-mounted host size: 372×111×500(mm)